الوصف
The GE IS200EDCFG1AED Exciter DC Feedback Board (EDCF) is a vital component of the GE EX2100 Excitation Control System.1 Its critical and isolated function is to accurately measure the generator’s Field Current (DC) and Field Voltage (DC) directly at the SCR (Thyristor) bridge.2
This high-accuracy, noise-immune feedback is paramount for the EX2100 controller to maintain stable closed-loop control of the exciter bridge and regulate the generator’s output.3
⚙️ Core Functions and Isolated Measurement
The EDCF board is situated in the high-power section of the exciter cabinet, demanding robust signal isolation.
1. Field Current Measurement
- Method: Measures the voltage drop across a DC current shunt located in the exciter bridge circuit.4
- Processing: This low-level analog signal is amplified and then converted into a frequency signal using a Voltage-Controlled Oscillator (VCO).
2. Field Voltage Measurement
- Method: Measures the high DC voltage across the exciter bridge terminals.
- Processing: The high voltage is safely scaled down using jumper-selectable settings (up to seven settings) to match the exciter’s maximum voltage, and then processed through a separate VCO.5
3. Isolated Communication (Fiber-Optic Link)
The most critical feature of the EDCF is how it transfers data to the control cabinet:
- The frequency-encoded current and voltage signals are transmitted to the main control panel via high-speed fiber-optic links (one fiber for current, one for voltage).6
- This fiber-optic link ensures complete electrical isolation and superior noise immunity, preventing the high-voltage noise from the bridge from interfering with the sensitive control electronics in the main rack.
🛠️ Technical Specifications
| Feature | Details |
| System | GE EX2100 Excitation Control System |
| Function | Measures Field DC Current and DC Voltage |
| Location | Exciter Power Conversion Cabinet (PCC) |
| Communication | Fiber-Optic Link (Transmits to the EISB board) |
| Current Scaling | Accepts maximum shunt input of 500 mV. |
| Voltage Scaling | Jumper-Selectable for various exciter voltage levels. |
| Revision | The suffix G1AED denotes the specific hardware and software revision. |
The IS200EDCFG1AED is therefore the highly accurate and isolated data source that enables the EX2100 to effectively implement Automatic Voltage Regulation (AVR).