GE IS200EPBPG1AAC Power Backplane Board

د.إ8,888.00

The primary function of the IS200EPBPG1AAC is to serve as the central power bus for the control electronics within the exciter cabinet.

  • Logic Power Distribution: It manages and distributes the required logic-level DC voltages (such as 2$\text{+5 V DC}$, 3$\text{+15 V DC}$, and 4$\text{+24 V DC}$) to the three primary controller units (M1, M2, and C) in redundant (TMR) EX2100 systems.5
  • Power Supply Housing: The backplane provides slots and connectors for the Exciter Power Supply Modules (EPSM)—typically three of them, one for each controller section (M1, M2, C).6 These EPSM modules convert an external 7$\text{125 V DC}$ supply into the needed logic-level voltages.8
  • Ground Detection: The board also incorporates connectors for the Exciter Ground Detector Modules (EGDM), which monitor for ground faults in the exciter’s power circuitry.9
  • Physical Backbone: It acts as the physical mounting structure for the EPSM and EGDM modules and connects them to the main Exciter Control Backplane (EBKP).
التصنيف:

الوصف

The GE IS200EPBPG1AAC Power Backplane Board (EPBP) is a critical infrastructure component in the EX2100 Excitation Control System, which is part of the larger GE Mark VI Speedtronic platform used to control large generator excitation systems.1

⚡ Core Function: Power Distribution

The primary function of the IS200EPBPG1AAC is to serve as the central power bus for the control electronics within the exciter cabinet.

  • Logic Power Distribution: It manages and distributes the required logic-level DC voltages (such as 2$\text{+5 V DC}$, 3$\text{+15 V DC}$, and 4$\text{+24 V DC}$) to the three primary controller units (M1, M2, and C) in redundant (TMR) EX2100 systems.5
  • Power Supply Housing: The backplane provides slots and connectors for the Exciter Power Supply Modules (EPSM)—typically three of them, one for each controller section (M1, M2, C).6 These EPSM modules convert an external 7$\text{125 V DC}$ supply into the needed logic-level voltages.8
  • Ground Detection: The board also incorporates connectors for the Exciter Ground Detector Modules (EGDM), which monitor for ground faults in the exciter’s power circuitry.9
  • Physical Backbone: It acts as the physical mounting structure for the EPSM and EGDM modules and connects them to the main Exciter Control Backplane (EBKP).

📋 Key Specifications

Specification Detail
Name Exciter Power Backplane Board (EPBP)
Series EX2100 Excitation Control System
Input Power Source $\text{125 V DC}$ (Typically supplied from the Exciter Power Distribution Module, EPDM)
Distributed Power $\text{+5 V DC}$, $\text{+15 V DC}$, $\text{+24 V DC}$ (Logic Power)
Module Capacity Holds three Exciter Power Supply Modules (EPSM) and three Exciter Ground Detector Modules (EGDM).
Revision The “AAC” in the part number indicates a specific hardware/firmware revision.

In short, the IS200EPBPG1AAC is essential because it guarantees that the entire control system—particularly the redundant digital signal processors and I/O boards—receives clean, isolated, and reliable power necessary for continuous, stable generator operation.