WOODWARD 8237-2492

Technical Specifications

 

Parameter Value
Product Type Overspeed Protection Device / Safety PLC Module
Manufacturer Woodward
Model/Part Number 8237-2492 (MicroNet Safety Module – MSM series)
Turbine Types Gas, Steam, and Water Turbines
Control System Digital, Microprocessor-based, Integrated Safety PLC
Safety Architecture Triple Modular Redundancy (TMR), 2-out-of-3 (2oo3) Voted Inputs
Safety Certification IEC61508 SIL-3, API 670, API 612
Mounting Bulkhead Mount
Power Input High Voltage (HV) / Low Voltage (LV) compatible (e.g., 90–240 Vac / 100–150 Vdc or 18–32 Vdc)
Relay Type Independent Relays (Outputs)
Input Sensors Active or Passive MPUs (Magnetic Pick-Up Units), Proximity probes
Protection Features Overspeed, Overacceleration, Speed Loss detection
Communication Modbus (serial)
Diagnostics Real-time alarms, Alarm/Trip/Overspeed logs
Testing Manual and Automatic Online Testing
Maintenance Online module replacement
Environmental Resistant to sulfur, H2S, SO2 gases (Class 3C2), IP56 ingress protection
Operating Temperature –20 to +60 °C (–4 to +140 °F)
Response Time Fast (typically <12 milliseconds for critical trips)
Speed Range 0.5 to 32,000 RPM (up to 80,000 RPM for some configurations)
التصنيف:

الوصف

The WOODWARD 8237-2492 is a highly specialized and critical safety component within Woodward’s MicroNet Safety Module (MSM) series. It functions as a sophisticated Safety PLC with integrated overspeed protection, specifically designed to ensure the safe and reliable operation of steam, gas, and hydro turbines. It continuously monitors turbine speed and acceleration, initiating an emergency shutdown if unsafe conditions are detected.

This particular model, the 8237-2492, is characterized by its bulkhead mount design, its ability to accept High Voltage (HV) and Low Voltage (LV) power inputs (providing power flexibility), and its use of independent relays for its outputs. Like other MicroNet Safety Modules, it features a triple modular redundant (TMR) architecture for its inputs, ensuring high reliability.


 

Optimized SEO Titles

 

  1. WOODWARD 8237-2492: MicroNet Safety Module (MSM) Bulkhead Mount HV/LV
  2. 8237-2492 Woodward: Digital Turbine Overspeed Protection with Independent Relays
  3. WOODWARD 8237-2492: Triple Modular Redundant Safety PLC for Turbines
  4. Buy 8237-2492: Genuine Woodward MSM for Critical Applications
  5. 8237-2492 for Sale: Enhancing Turbine Safety and Reliability
  6. WOODWARD 8237-2492: IEC61508 SIL-3 Certified Turbine Safety Device
  7. MicroNet Safety Module 8237-2492: Essential for Turbine Shutdown Systems
  8. 8237-2492 Woodward: Advanced Acceleration and Overspeed Detection
  9. WOODWARD 8237-2492: Comprehensive Turbine Diagnostics & Event Logging
  10. 8237-2492 Control Board: High Availability Turbine Management

 

Brief Product Description

 

The WOODWARD 8237-2492 is a MicroNet Safety Module (MSM), acting as a sophisticated safety PLC with integrated overspeed protection. It’s engineered for critical industrial safety applications, precisely monitoring the speed and acceleration of turbine rotors (steam, gas, or hydro). It boasts a triple modular redundant (2-out-of-3 voted) input architecture, ensuring highly reliable and precise overspeed detection. This specific model is designed for bulkhead mounting, supports High Voltage (HV) and Low Voltage (LV) power inputs for power flexibility, and employs independent output relays to issue safe shutdown commands to the turbine’s trip system. It also includes Modbus communication for seamless diagnostics and remote integration into plant control systems.

  • Product Type: Overspeed Protection Device / Safety PLC Module (MicroNet Safety Module – MSM)
  • Manufacturer: Woodward
  • Model/Part Number: 8237-2492 (MicroNet Safety Module series)
  • Primary Function: Turbine overspeed and overacceleration protection, safe shutdown, and integrated safety functions.
  • Key Features: Triple modular redundancy (2oo3 voted inputs), digital speed control, independent relays, Modbus communication, bulkhead mount, HV/LV power input.

 

Detailed Product Description

 

In critical industrial processes where large rotating machinery like turbines are integral to operations, preventing an uncontrolled overspeed event is paramount for safety and operational continuity. Such events can lead to catastrophic mechanical failure, severe equipment damage, and significant safety hazards. The WOODWARD 8237-2492 MicroNet Safety Module (MSM) is engineered precisely for these high-stakes environments. It’s not merely a speed monitoring device; it’s a sophisticated, highly reliable, and fault-tolerant safety system designed to provide the ultimate layer of protection for valuable turbine assets.

In a recent consultation for a power plant, the existing turbine safety system needed an upgrade to meet modern safety integrity levels and enhance diagnostic capabilities. The Woodward MicroNet Safety Module (MSM) series, specifically the 8237-2492, was an ideal solution. Its bulkhead mount design allowed for efficient installation directly on a wall or skid near the turbine, simplifying wiring and reducing installation time. The flexibility of accepting both High Voltage (HV) and Low Voltage (LV) power inputs was a significant advantage, allowing seamless power integration into the plant’s diverse electrical infrastructure. Furthermore, the use of independent relays on the output side, combined with the triple modular redundant (TMR) inputs, provided multiple layers of protection, ensuring that the system would reliably execute a trip when a genuine hazardous condition occurred, while minimizing nuisance trips. This system significantly enhanced the plant’s overall safety posture and operational reliability.

 

Uncompromising Safety with Digital Control and Redundancy

 

The WOODWARD 8237-2492 is built upon the robust foundation of the MicroNet Safety Module (MSM) series’ advanced safety architecture, delivering superior protection:

  • Digital Speed and Acceleration Monitoring: This module precisely monitors the turbine rotor’s speed and rate of acceleration. It typically receives signals from active or passive Magnetic Pick-Up Units (MPUs) or proximity probes. This digital approach ensures high accuracy and rapid response times, which are crucial for detecting and reacting promptly to hazardous conditions.
  • Overspeed and Overacceleration Protection: Its core function is to detect when the turbine’s speed or its acceleration rate exceeds pre-defined safety setpoints. Upon detection, it quickly issues a trip command to the turbine’s emergency trip valve(s) or other shutdown mechanisms to prevent a runaway condition.
  • Triple Modular Redundancy (TMR) for Inputs (2-out-of-3 Voting): This is a defining characteristic of the MicroNet Safety Module (MSM) series. The system employs three independent channels for speed sensing and processing. For a trip condition to be declared, at least two out of the three channels must independently confirm the overspeed or overacceleration event. This 2oo3 voting logic significantly enhances system reliability by minimizing the risk of nuisance trips due to a single sensor or module fault, while still ensuring a safe shutdown when a genuine hazardous condition exists.
  • IEC61508 SIL-3 Certified: This certification signifies that the 8237-2492 meets the most rigorous international standards for functional safety. Achieving Safety Integrity Level 3 means the device has an extremely low probability of dangerous failure, making it suitable for the most critical Safety Instrumented Functions (SIF) in demanding industrial applications. It also adheres to industry standards such as API 670 and API 612.
  • Independent Relays (Output): This model specifically features independent relays for its trip outputs. This design provides distinct, non-voted outputs that can be wired to separate trip solenoids or systems, offering flexibility for integration into various turbine trip architectures and allowing for more granular control over different shutdown actions.

 

Design and Features for Flexible Integration and Maintenance

 

The 8237-2492 is designed for practical industrial application and ease of maintenance:

  • Bulkhead Mount Design: This variant is specifically designed for bulkhead mounting on a wall or skid, which is common in field enclosures or local equipment skids, providing a robust and secure installation directly near the turbine.
  • High Voltage (HV) and Low Voltage (LV) Power Inputs: The module can be flexibly powered by either a High Voltage (HV) source (e.g., 90–240 Vac / 100–150 Vdc) or a Low Voltage (LV) source (e.g., 18–32 Vdc). This versatility simplifies power integration into diverse plant electrical systems.
  • Modbus Communication: Equipped with Modbus (serial) communication, the device can seamlessly integrate with Distributed Control Systems (DCS), SCADA systems, or other plant-wide monitoring platforms. This enables remote monitoring of turbine speed, alarm statuses, detailed diagnostics, and historical event logs.
  • Online Testing and Repair: A significant advantage of the MicroNet Safety Module (MSM) system is its ability to perform online testing of its functionality and speed sensors without requiring a turbine shutdown. Individual modules can often be replaced while the system remains online, significantly minimizing operational downtime during maintenance.
  • Comprehensive Logging: The device stores detailed historical logs of all trips, alarms, overspeed events, and trip valve response times in non-volatile memory. This data is invaluable for post-event analysis, root cause identification, and compliance reporting.
  • Environmental Robustness: Engineered for harsh industrial environments, it features robust construction and often includes conformal coating to protect against common contaminants like sulfur, H2S, and SO2 gases (rated for Class 3C2 environments and typically IP56 ingress protection when properly installed).

 

Technical Specifications

 

Parameter Value
Product Type Overspeed Protection Device / Safety PLC Module
Manufacturer Woodward
Model/Part Number 8237-2492 (MicroNet Safety Module – MSM series)
Turbine Types Gas, Steam, and Water Turbines
Control System Digital, Microprocessor-based, Integrated Safety PLC
Safety Architecture Triple Modular Redundancy (TMR), 2-out-of-3 (2oo3) Voted Inputs
Safety Certification IEC61508 SIL-3, API 670, API 612
Mounting Bulkhead Mount
Power Input High Voltage (HV) / Low Voltage (LV) compatible (e.g., 90–240 Vac / 100–150 Vdc or 18–32 Vdc)
Relay Type Independent Relays (Outputs)
Input Sensors Active or Passive MPUs (Magnetic Pick-Up Units), Proximity probes
Protection Features Overspeed, Overacceleration, Speed Loss detection
Communication Modbus (serial)
Diagnostics Real-time alarms, Alarm/Trip/Overspeed logs
Testing Manual and Automatic Online Testing
Maintenance Online module replacement
Environmental Resistant to sulfur, H2S, SO2 gases (Class 3C2), IP56 ingress protection
Operating Temperature –20 to +60 °C (–4 to +140 °F)
Response Time Fast (typically <12 milliseconds for critical trips)
Speed Range 0.5 to 32,000 RPM (up to 80,000 RPM for some configurations)


 

Key Applications

 

The WOODWARD 8237-2492 is a vital safety component employed in a wide array of high-stakes industrial applications:

  • Power Generation: Providing robust primary and backup overspeed protection for gas, steam, and hydro turbines in diverse power plant configurations worldwide.
  • Oil & Gas: Safeguarding gas turbines driving critical compressors in pipelines, processing plants, and offshore platforms.
  • Petrochemical Industry: Protecting turbine-driven machinery vital to chemical manufacturing and refining operations.
  • Marine Propulsion: Used in large marine vessels for highly reliable turbine overspeed protection systems.
  • Industrial Plants: Any facility that relies on large industrial turbines where safety, continuous operation, and regulatory compliance are paramount.