Triconex 9563-810

Technical Specifications

 

Feature Details
Product Type External Termination Panel
Part Number 9563-810
Input Type Digital Input
Nominal Voltage 24 VDC
Points per Panel 16
Panel Type Commoned
Fuse Protection Yes, with blown-fuse indicator
Compatible Modules 3503E, 3505E
Mounting DIN-rail mountable
التصنيف:

الوصف

The Triconex 9563-810 is a Digital Input (DI) Termination Panel designed for use with Triconex safety systems. Its purpose is to provide an interface between the Triconex I/O module and the field wiring from your sensors and other devices.


 

What It Is and How It Works

 

This termination panel acts as an organized junction box for your field wiring. Instead of connecting each individual field wire directly to the I/O module, you connect them to the screw terminals on the 9563-810 panel. The panel then connects to the Triconex Digital Input module via a single, pre-assembled cable, which simplifies installation and maintenance.

A key feature of the 9563-810 is its design for 24 VDC commoned applications. This means it provides common power terminals for a group of inputs, which is a common configuration in many industrial control systems.

 

Key Features and Compatibility

 

  • Function: It is a Digital Input (DI) Termination Panel that receives signals from field devices like limit switches and push buttons.
  • Voltage: The panel is rated for 24 VDC.
  • Points: The panel provides 16 input points and includes commoned power terminals (PWR+ and PWR-).
  • Module Compatibility: Since the compatible Digital Input modules (such as the 3503E and 3505E) are 32-point modules, you must use two 9563-810 panels for each module to handle all 32 points.
  • Protection: Each input point on the panel is protected by a fuse, and a blown-fuse indicator is included to simplify troubleshooting.
  • Mounting: It is designed for DIN-rail mounting.

 

Technical Specifications

 

Feature Details
Product Type External Termination Panel
Part Number 9563-810
Input Type Digital Input
Nominal Voltage 24 VDC
Points per Panel 16
Panel Type Commoned
Fuse Protection Yes, with blown-fuse indicator
Compatible Modules 3503E, 3505E
Mounting DIN-rail mountable